Skip to main content

Diesel generators 1000 kW and up

Megawatt sets for plants, mines, large data centres and remote sites where the generator is the main source of power, not the backup.

54 models from 1000 to 3000 kW on Weichai, Yuchai, Cummins, Perkins and Baudouin engines. Filter by engine and build, and open any one for its full datasheet.

Engine
Sort

54 of 54 models

SP-1000C Cummins · KTA50-G3 Prime 1000 kW Standby 1100 kW kVA 1250 Fuel 254 L/h Open, canopied
SP-1000C1 Cummins · QSK38-G5 Prime 1000 kW Standby 1100 kW kVA 1250 Fuel 274 L/h Open, canopied
SP-1000P Perkins · 4012-46TWG2A Prime 1000 kW Standby 1100 kW kVA 1250 Fuel 258.1 L/h Open, canopied
SP-1000WC Weichai · 12M33D1210E200 Prime 1000 kW Standby 1100 kW kVA 1250 Fuel 244.7 L/h Open, canopied
SP-1000YC Yuchai · YC12VTD1680-D30 Prime 1000 kW Standby 1100 kW kVA 1250 Fuel 271 L/h Open, canopied
SP-1000YC3 Yuchai · YC6C1660-D31 Prime 1000 kW Standby 1100 kW kVA 1250 Fuel 271 L/h Open, canopied
SP-1375BD Baudouin · 12M33G1400-5 Prime 1000 kW Standby 1100 kW kVA 1250 Fuel 233.3 L/h Open, canopied
SP-1100C Cummins · KTA50-G8 Prime 1100 kW Standby 1200 kW kVA 1375 Fuel 289 L/h Open, canopied
SP-1100P Perkins · 4012-46TWG3A Prime 1100 kW Standby 1210 kW kVA 1375 Fuel 279.1 L/h Open, canopied
SP-1100WC Weichai · 12M33D1320E200 Prime 1100 kW Standby 1210 kW kVA 1375 Fuel 269.2 L/h Open, canopied
SP-1100YC Yuchai · YC12VTD1830-D30 Prime 1100 kW Standby 1210 kW kVA 1375 Fuel 307 L/h Open, canopied
SP-1500BD Baudouin · 12M33G1500-5 Prime 1100 kW Standby 1200 kW kVA 1375 Fuel 272.1 L/h Open, canopied
SP-1200C Cummins · KTA50-GS8 Prime 1200 kW Standby 1320 kW kVA 1500 Fuel 309 L/h Open, canopied
SP-1200P Perkins · 4012-46TAG2A Prime 1200 kW Standby 1320 kW kVA 1500 Fuel 299 L/h Open, canopied
SP-1200WC Weichai · 12M33D1500E310 Prime 1200 kW Standby 1320 kW kVA 1500 Fuel — Open, canopied
SP-1200YC Yuchai · YC12VTD2000-D30 Prime 1200 kW Standby 1320 kW kVA 1500 Fuel 335 L/h Open, canopied
SP-1650BD Baudouin · 12M33G1650-5 Prime 1200 kW Standby 1320 kW kVA 1500 Fuel 288.6 L/h Open, canopied
SP-1300WC Weichai · 16M33D1580E310 Prime 1300 kW Standby 1430 kW kVA 1625 Fuel — Open, canopied
SP-1320C Cummins · QSK50-G7 Prime 1320 kW Standby 1452 kW kVA 1650 Fuel 349 L/h Open, canopied
SP-1340C1 Cummins · KTA50-G15 Prime 1340 kW Standby 1500 kW kVA 1675 Fuel 330 L/h Open, canopied
SP-1350P Perkins · 4012-46TAG3A Prime 1350 kW Standby 1500 kW kVA 1687.5 Fuel 367.3 L/h Open, canopied
SP-1350YC1 Yuchai · YC16VTD2270-D30 Prime 1350 kW Standby 1500 kW kVA 1688 Fuel 374.4 L/h Open, canopied
SP-1400WC Weichai · 16M33D1680E310 Prime 1400 kW Standby 1540 kW kVA 1750 Fuel 339.3 L/h Open, canopied
SP-1900BD Baudouin · 16M33G1900-5 Prime 1400 kW Standby 1520 kW kVA 1750 Fuel 316.7 L/h Open, canopied
SP-1480P Perkins · 4016TAG1A Prime 1480 kW Standby 1628 kW kVA 1850 Fuel 381.3 L/h Open, canopied
SP-1500C Cummins · QSK60-G3 Prime 1500 kW Standby 1650 kW kVA 1875 Fuel 398 L/h Open, canopied
SP-1500C1 Cummins · KTA50-G16A Prime 1500 kW Standby 1650 kW kVA 1875 Fuel 397 L/h Open, canopied
SP-1500WC Weichai · 16M33D1800E310 Prime 1500 kW Standby 1650 kW kVA 1875 Fuel 363.5 L/h Open, canopied
SP-1500YC1 Yuchai · YC16VTD2510-D30 Prime 1500 kW Standby 1650 kW kVA 1875 Fuel 374.4 L/h Open, canopied
SP-2065BD Baudouin · 16M33G2000-5 Prime 1500 kW Standby 1650 kW kVA 1875 Fuel 339.3 L/h Open, canopied
SP-1600C Cummins · QSK60-G4 Prime 1600 kW Standby 1760 kW kVA 2000 Fuel 433 L/h Open, canopied
SP-1600P Perkins · 4016TAG2A Prime 1600 kW Standby 1760 kW kVA 2000 Fuel 434 L/h Open, canopied
SP-1600WC Weichai · 16M33D1980E310 Prime 1600 kW Standby 1760 kW kVA 2000 Fuel 385.9 L/h Open, canopied
SP-1600YC Yuchai · YC16VTD2700-D30 Prime 1600 kW Standby 1760 kW kVA 2000 Fuel 432.5 L/h Open, canopied
SP-1650WC Weichai · 20M33D2020E310 Prime 1650 kW Standby 1815 kW kVA 2063 Fuel 434.1 L/h Open, canopied
SP-2250BD Baudouin · 16M33G2250-5 Prime 1650 kW Standby 1800 kW kVA 2062.5 Fuel 361.9 L/h Open, canopied
SP-1800C Cummins · QSK60-G21 Prime 1800 kW Standby 2000 kW kVA 2250 Fuel 454 L/h Open, canopied
SP-1800P Perkins · 4016-61TRG3 Prime 1800 kW Standby 2000 kW kVA 2250 Fuel 467.6 L/h Open, canopied
SP-1800WC Weichai · 12M55D2210E310 Prime 1800 kW Standby 2000 kW kVA 2250 Fuel 434.1 L/h Open, canopied
SP-1800WC1 Weichai · 20M33D2210E310 Prime 1800 kW Standby 2000 kW kVA 2250 Fuel 434.1 L/h Open, canopied
SP-1800YC Yuchai · YC16VC3000-D31 Prime 1800 kW Standby 2000 kW kVA 2250 Fuel 485 L/h Open, canopied
SP-1800YC3 Yuchai · YC12VC3000-D30 Prime 1800 kW Standby 2000 kW kVA 2250 Fuel 493.3 L/h Open, canopied
SP-2000C Cummins · QSK78-G18 Prime 2000 kW Standby 2200 kW kVA 2500 Fuel 510 L/h Open, canopied
SP-2000WC Weichai · 12M55D2450E310 Prime 2000 kW Standby 2200 kW kVA 2500 Fuel 482 L/h Open, canopied
SP-2000YC Yuchai · YC16VC3300-D31 Prime 2000 kW Standby 2200 kW kVA 2500 Fuel 533 L/h Open, canopied
SP-2200C Cummins · QSK78-G9 Prime 2200 kW Standby 2420 kW kVA 2750 Fuel 556 L/h Open, canopied
SP-2200WC Weichai · 12M55D2700E310 Prime 2200 kW Standby 2420 kW kVA 2750 Fuel 572 L/h Open, canopied
SP-2200YC Yuchai · YC16VC3600-D31 Prime 2200 kW Standby 2420 kW kVA 2750 Fuel 639 L/h Open, canopied
SP-2250WC Weichai · 16M55D2750E310 Prime 2250 kW Standby 2475 kW kVA 2813 Fuel — Open, canopied
SP-2400C Cummins · QSK78-G6 Prime 2400 kW Standby 2640 kW kVA 3000 Fuel 592 L/h Open, canopied
SP-2400WC Weichai · 12M55D2900E310 Prime 2400 kW Standby 2640 kW kVA 3000 Fuel — Open, canopied
SP-2400YC Yuchai · YC16VC4000-D31 Prime 2400 kW Standby 2640 kW kVA 3000 Fuel 673.9 L/h Open, canopied
SP-2600WC Weichai · 16M55D3300E310 Prime 2600 kW Standby 2860 kW kVA 3250 Fuel — Open, canopied
SP-3000WC Weichai · 16M55D3600E310 Prime 3000 kW Standby 3300 kW kVA 3750 Fuel — Open, canopied

Side by side

Baudouin model numbers give apparent power in kVA; prime power in kW is in each set’s specs.

How to size the set

  1. Add up what runs at once, in kW. A motor, pump or compressor draws three to six times its rating for a few seconds as it starts, and the set has to carry that too.

  2. Size on prime power if the set will run for hours or every day. Standby power is for emergencies only, for a limited number of hours a year.

  3. Leave 20–30% headroom, but not much more: a diesel that runs for long below about a third of its rating soots up and wears faster.

  4. kVA is not kW. At the usual power factor of 0.8, kW = kVA × 0.8, so a 250 kVA set gives 200 kW.

Tell us the load. We size the set.

A written quote, a free site survey, and a straight answer on lead time.

Call now: +998 95 515 68 88