Diesel generators 400–1000 kW
Sets for a shopping mall, a large hospital, a data centre or a plant, often built into a container and installed as part of the building’s power system.
58 models from 400 to 900 kW on Weichai, Yuchai, Cummins, Perkins and Baudouin engines. Filter by engine and build, and open any one for its full datasheet.
58 of 58 models
No set matches these filters.
Baudouin model numbers give apparent power in kVA; prime power in kW is in each set’s specs.
How to size the set
Add up what runs at once, in kW. A motor, pump or compressor draws three to six times its rating for a few seconds as it starts, and the set has to carry that too.
Size on prime power if the set will run for hours or every day. Standby power is for emergencies only, for a limited number of hours a year.
Leave 20–30% headroom, but not much more: a diesel that runs for long below about a third of its rating soots up and wears faster.
kVA is not kW. At the usual power factor of 0.8, kW = kVA × 0.8, so a 250 kVA set gives 200 kW.
Tell us the load. We size the set.
A written quote, a free site survey, and a straight answer on lead time.